|
|
TM 32-5410-221-14&P
Section V. TROUBLESHOOTING
WARNING
5-7
Dangerous voltage is present in the
281/G, their probable causes, and the corrective action
electrical circuits. Death on contact
required at the organizational level of maintenance as
may result.
Use all safety
authorized by the MAC. Any trouble that is beyond the
precautions and be extremely careful
scope of organizational maintenance must be referred to
when
performing
electrical
direct support maintenance.
troubleshooting and repairs.
Table 5-2. Organizational Maintenance Troubleshooting
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
ELECTRICAL -
1. NO POWER IN SHELTER WHEN MAIN CIRCUIT BREAKER IS ON.
Step 1.a. Central or Commercial Power. See if nearby facilities that are using same main source have
power.
If main power is OFF, switch to auxiliary power until main power is restored.
b. Individual Generator Power. See if generator is operating properly. Refer to applicable manual.
Step 2. Inspect main power cable for loose or broken connections.
Reconnect, tighten, repair, or replace as necessary.
Step 3. Check output, or make point-to-point continuity test from main power source to main circuit
breaker, until the malfunction is isolated.
Repair malfunction or replace defective component.
2. MAIN CIRCUIT BREAKER IS ON BUT THERE IS NO POWER TO A LIGHT UNIT OR RECEPTACLE.
Step 1. Check to see if in-line contact components (circuit breakers, switches, etc.) are ON. See wiring
diagram, figure 6-1.
If any in-line contact components are OFF, reset to ON.
Step 2. Check output, or make point-to-point continuity checks from main circuit breaker to light unit or
receptacle, until the malfunction is isolated.
Repair malfunction or replace defective component.
3. POWER TO LIGHT UNIT, BUT BULB(S) DOES NOT LIGHT.
Step 1. Check to see that bulb is tight in socket and making good contact.
If bulb is loose in socket, tighten it.
5-7
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |