|
|
TM 32-5811-024-14&P
5-13. AGE Display.
5-14. Control-Indicator Test Function.
a. General. (See figure FO-15) Control-indicator test CCA A9 tests the communication processor control-indicator.
Two tests may be performed: the first test requires entering a code that lights all indicators on the control-indicator. This
test is activated by setting the digital processor test set CONT. IND. TEST switch to the DISP. position, and pressing the
UPDATE switch. The second test, performed with the digital processor test set CONT. IND. TEST switch in the NORM
position, tests all switches and status indicators, as well as the input and output control logic of the control-indicator. This
test involves setting the control-indicator switches to provide a unique communication processor control-indicator output
status (CIOSTS) word.
When the 32-bit CIOSTS word is serially transferred to CCA A9 as high control-indicator data (HOD), the test
response matrix circuits on CCA A9 convert the input into a 16-bit CIISTS (control-indicator input status) word, which is
serially transferred back into the control-indicator via the HID (high input data) lines. This coded word lights the control-
indicator status lamp selected. The lighting of the appropriate control-indicator status lamp verifies proper operation of
the communication processor control-indicator switches.
b. Detailed Description. Figure FO-6 shows a simplified functional diagram of the control-indicator test circuits of
the digital processor test set. Generally, the 32-bit word, resulting from unit-under-test control-indicator switching, is
serially transferred into control indicator test CCA A9. This data word (CIOSTS) provides a parallel address input to the
test response matrix. The matrix responds to this address input by providing a 1-of-16 coded response word output. The
matrix will drive only 1 of the 16 response word bits high as a result of the 32-bit address input. This response word is
then serially transferred back to the unit-under-test control-indicator, where it will light the appropriate status lamp.
The following is a detailed description of the circuit activity (see figure 5-8 and figure FO-6) that occurs during a
typical test sequence:
(1) Time state T0. Setting UPDATE switch S14 drives the output of IHUD line receiver U35A high. This
positive transition triggers update single-shot U34B. U34B responds by generating a 10- negative pulse. This pulse is
s
transferred to the logic control circuits of the communication processor control-indicator CCA A2 via line
5-22
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |