TM 32-5410-221-14&P
Table 3-1. Operator's Controls - Continued
Controls, indicators, or connectors
Description
Function
CB11 receptacle equipment rack No. 4
Provides ac power to equipment rack No. 4.
CB2, CB4, CB6 air conditioner
50 amperes
Provides 220 Vac power for air conditioner.
CB8 front wall road
15 amperes
Provides ac power to receptacles on roadside and front wall.
CB10 roadside equipment receptacles
15 amperes
Provides ac power to receptacles on roadside.
CB12 receptacle equipment rack No. 5
15 amperes
Provides ac power to equipment rack No. 5.
Section II. OPERATION UNDER USUAL CONDITIONS
For Trane model air conditioners,
3-3
ENERGIZING AC CIRCUITS.
step d will energize the crankcase
heater to vaporize any refrigerant
CAUTION
present in the oil.
Failure to perform step 3-3a may
result in a power source overload
due to initial current drain.
10).
e. Jog fan motor by turning selector switch to
a. Set all circuit breakers and electrical switches to
VENTILATE and immediately back to OFF. This checks
OFF.
for binding or interference in the fan.
b. Activate main power source. Refer to the
f. Set temperature control to desired temperature.
applicable manual for generator operation. Refer to
g. Set selector switch to COOL, LO HEAT, HIGH
local directives for local or commercial power.
HEAT, or VENTILATE for desired operation.
c. Set shelter MAIN POWER SWITCH to ON.
d. Set LIGHTS circuit breaker No. 3 to ON to
(1) For heating or cooling with 100 percent
energize both incandescent and blackout light circuits.
recirculated air, close damper door and open intake
e. Set each light fixture toggle switch to ON to turn
grille damper.
each incandescent light on.
(2) For heating or cooling with fresh makeup
f. Raise blackout limit switch arm to turn two
air, open damper door and partially close intake grille
damper.
blackout lights on and two incandescent lights off. Use
hasp to hold arm up.
(3) For heating or cooling with fresh makeup
air drawn through chemical, biological, and radiological
g. Set circuit breakers Nos. 1, 2, 5 and 7 through
filter unit when outside air is contaminated, close
11 to ON to energize convenience outlets and
damper door and partially close intake grille damper.
equipment power receptacles.
(4) For ventilating operation, open damper
h. Set AIR CONDITIONER circuit breaker to ON to
door and close intake grille damper.
energize air conditioner receptacle.
3-4
AIR CONDITIONER OPERATION. Operate the
h. To stop the air conditioner, proceed as follows:
air conditioner as follows:
(1) Set selector switch to OFF.
a. Ensure that air conditioner external canvas
CAUTION
cover is rolled up and secured with tiedown snap.
b. Check to see that internal and external air flow
For Trane model air conditioners,
vent openings are free from obstructions.
step (2) will cause refrigerant to
c. Set selector switch to OFF.
condensate in the crankcase and mix
with the oil.
NOTE
3-2
|