ELECTRICAL
SERVICE
CARD NO.
MAN
WORK
WORK UNIT
28 Day Inspection
INSPECTION
POWER
OFF
OUT
1-012
MIN
AREA
SYSTEM
SUB-SYS
REQUIREMENTS
(Cont'd from card 1-012)
WARNING
Dangerous voltages are present on the back of the Power Board
panels. Do not attempt to commence inspection until voltage
sources are removed as described below.
0030
C.
Interior. On rectifier Disconnect Panel 1A13, place the three circuit
breakers CB1, CB2 and CB3 to the OFF position. On Battery Disconnect
Panel 1A14, place circuit breaker CB1 to the OFF position. Hang red tags
on the four circuit breakers marked "Warning do not activate".
CARD NO.
WORK AREAS
TYPE MECH RQR
MECH NO.
CARD TIME
PUBLICATION
T.O. 31W2-4-203-6WC-1
NUMBER
T.M. 11-6130-363-14-1/2
1-012