TM 11-5920-252-24
2. Steps 2 through 4 In Table 3-1 are to be performed at each of the 4 binding
posts forchannels 1 through 12. Step 1 will verify that the TS-3760/G is
operable.
3.15.
TEST SET S-3760/G IN AUTO MODE
TABLE 3-1. TS-3760/G AUTO (Automatic) Mode
Step
TS-3780/G Procedure
TS-3760/G Indication
Status/Condition
1
POWER SWITCH ON
Red OV light on if audible
TS3760/G ok
sound heard press RESET
switch.
2
Red test lead to
a. Green TZOK light on.
a. Go to step 3.
binding post for
Red OV light off.
CHANNEL 1
b. Audible tone from
b. Possible faulty arrester.
speaker. Red light on.
3
Press START switch
a. Green SGOK light on.
a. Go to step 4.
b. Audible garble sound
b. Possible faulty arrester.
from speaker and green
SGOK light off.
4
Connect red test lead
a. Same as step 2a above.
a. Repeat step.2 and 3
to another binding
above for all input lines of
post.
the arrester.
b. Same as step 2b above.
b. Same as step 2b above.
3-14
|