TM 11-5895-1123-34
(6) Mount the reversing network with the jacks
insert and tighten the four mounting screws to secure the
to the rear of the front panel, and insert and tighten the
patch panel to the rack.
b. Connect the 230 cables to the rear of the patch
two mounting screws through the jacks.
(7) Swing the patch panel closed and tighten
panel with the Trompeter RT-4S and RT-4L tools.
c. Close the patch panel and tighten the two
the two captive screws to hold it in place.
captive screws to secure it to the rack.
3-16. Replacement of Communications Data Patch
Panel SM-A-936517
a. Position the patch panel to the front of the rack,
Section V. MAINTENACE OF COMMUNICATIONS VF
PATCH PANEL SM-A-935851
a. Loosen the eight captive screws on the front
3-17.
Removal of Communications VF Patch Panel
panel of the VF patch panel.
SM-A-935851
b. Pull slowly forward on the patch panel to the
WARNING
point where resistance is met.
Two persons are required to perform
c. Loosen the 14 captive screws and remove the
this procedure due to the weight of the
panel covering access port located on the right side of
unit.
rack 8 above the central distribution frame.
CAUTION
d. Refer to figure 3-1 to tag and remove the cables
The VF patch panel can only be
from the rear of the patch panel unit. Remove and tag
extended two to four inches from the
the cables in reverse order (12 thru 1) by reaching
rack prior to disconnecting the 12 cables
through the access port.
at the rear of the patch panel unit.