TB 43-0199
Segregate DS2 from STB, HTH, and other oxidizers. However, in the event that short term depot or garrison storage or
storage in field situations requires DS2 to be stored in the same area as STB, HTH, and oxidizers, separate DS2 from
these materials by at least 5 feet and add a splash-proof barrier in between. Aisles, and areas between DS2 and other
chemical defensive equipment must be at least 5 feet wide in order to clean up spills and to make the containers
accessible for inspection.
4-4. Storage Facilities.
4-4.1 General. Depot or garrison storage of DS2 can be in a number of different types of facilities, e.g., rooms within
buildings, attached buildings, general warehouses, and liquid warehouses. Requirements for each of these will be
discussed separately in paragraphs below.
4-4.2 Storage Quantities. The amount of DS2 that can be stored in each facility is dependent on the type of storage
area. Quantities are further governed by whether the storage area is unprotected or protected. Protected storage is that
which has automatic fire suppression equipment (sprinklers) installed.
a.
Rooms within buildings. Amounts permitted in rooms within buildings are outlined in Table 4.
TABLE 4. ALLOWABLE QUANTITIES FOR STORAGE
IN INDIVIDUAL ROOMS WITHIN BUILDINGS
Automatic Fire Protection
Fire Resistance
Maximum Floor Area
Total Allowable Quantities
Provided
- Gallons Sq Ft of Floor
Area
Yes
2 hr
500 sq ft
10
No
2 hr
500 sq ft
4
Yes
1 hr
150 sq ft
5
No
1 hr
150 sq ft
2
b.
Attached buildings. An attached building is one having only one common wall with another building having
other types of occupants. Walls between the storage area and other areas of the building shall have a fire-resistance
rating of not less than
8
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |