TM 5-3610-254-14
Table 4-2. ORGANIZATIONAL TROUBLESHOOTING (cont)
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
3. NO POWER AT ONE OR MORE EQUIPMENT RECEPTACLES
Step 1. Check position of the applicable RECEPTACLE circuit breaker in
the main power service box.
If necessary, set applicable RECEPTACLE circuit breaker to ON.
Step 2. Inspect for defective receptacle or faulty wire connections as
follows:
WARNING
Death or serious injury could result if electrical precautions are not taken when maintaining this
equipment. Be sure that power cables are unplugged/disconnected, that circuit breakers are set to
OFF, and that generator cables are unplugged/disconnected. Be sure the equipment is properly
grounded. Always have another person standing by who is familiar with electrical shock first aid.
a. Set applicable RECEPTACLE circuit breaker in main power service box to OFF.
b.
Remove three screws which attach receptacle cover to conduit box.
c.
Pull receptacle from conduit box and inspect receptacle and wiring connections.
If necessary, replace defective receptacle and secure wiring connections as follows:
(1) Tag and disconnect wires and remove receptacle.
(2) Remove tags and connect wires to new receptacle.
(3) Insert receptacle into conduit.
(4) Position receptacle cover and secure with screws.
(5) Set applicable RECEPTACLE circuit breaker in main power service box to ON.