Table 4-8. Performance and Troubleshooting Test for the Control Monitor Assembly -48V/20 Hz Assembly-Continued
Step
Operation
Normal indication
If indication abnormal
e. Set switch 5 (S5) to ON and then to OFF
UNIT 1 ON LINE indicator
Replace DS3.
lights.
f. Set switch 6 (S6) to ON and then to OFF
UNIT 2 ON LINE indicator
Replace DS4.
lights.
g. Set switch 7 to ON and then OFF
20-Hz GEN PRIME FAULT
Check DS7. Check CR4.
indicator lights and AUDI-
BLE ALARM sounds.
h Set switch 8 (S8) to ON and then to OFF
20-Hz GEN STBY FAULT
Check DSS8. Check CR5.
indicator lights and AUDI-
BLE ALARM sounds.
i. Set switch 9 (S10) to ON and then to OFF
20-Hz GEN PRIME
Check DSI 1. Check R9.
POWER ON indicator
lights.
j. Set switch 10 (S11) to ON and then to OFF
20-Hz GEN STBY POWER
Check DS12. Check R10.
ON indicator lights.
k. .Set switch 11(S9) to ON.
AUDIBLE ALARM sounds.
Check LS1. Check R13. Check
S3.
l. Set switch 11 to OFF.
AUDIBLE ALARM is silent.
m. On the UUT, set AUDIBLE ALARM switch to
AUDIBLE ALARM sounds.
Check LS1. Check R13. Check
TEST.
S3.
o. Set AUDIBLE ALARM switch to ON.
p. Press each indicator lamp.
Each indicator lamp should Check lamp and circuitry that
light when pressed.
does not light.
5
Control Monitor Timer Test:
a. On the UUT set the 20-Hz GEN POWER switches
to OFF.
b. On the test fixture, connect a cable from the oscillo-
scope CH-1 INPUT to test jack J11 (J16 P).
e. On the oscilloscope, set the controls as follows:
CHANNEL 1 INPUT VOLTSIDIV 10/cm (DC)
TIMEIDIV TRIGGER SOURCE EXT 2 SEC.
d. On the UUT, set the 20-Hz GEN POWER switches
The oscilloscope sweep starts Refer to figure 4-10.
to ON.
across the screen at a level
of 0 to -2 vdc. It should
remain at that level for 10
seconds minimum and then
fold to a level -14 to -20
vdc
e. On the UUT, set the 20-Hz GEN POWER switches
to OFF.
f. Set the AUDIBLEALARM switch to DISABLE.
UUT, the AUDIBLE
ALARM lamp lights.
g. Set the AUDIBLE ALARM switch to ON
UUT, the AUDIBLE
ALARM lamp goes out.
k. Disconnect UUT from test fixture.
4-20