APPENDIX F
OPERATION AND MAINTENANCE
OF SOLA CVDC POWER SUPPLY
TYPE 28-1561-2
F-l. General Description
and full load. The output voltage is regulated to
1% over an input line variation of 100 to 130
The SOLA CVDC Power Supply Type 28-1561-2
volts RMS.
is a regulated constant voltage power supply which
The power supply shall not be operated in an
is designed to furnish regulated dc voltage. Within
ambient of greater than 50 C or stored at a
the limits of the specifications, this regulated
temperature greater than 85 C.
supply will deliver regulated voltage despite
F-2. Principles of Operation (Figure F-I)
changes in input line voltage, line frequency, load
impedance and temperature as described in the
The heart of the regulator is the constant voltage
specification limits.
transformer. A constant-voltage transformer has a
The power supply consists of a constant voltage
magnetic core structure different from conventional
transformer (described in greater detail under
transformers. It has a magnetic shunt with a fixed
principles of operation), a rectifying means and a
air gap interposed between the primary and
filter circuit. The transformer not only converts
secondary windings. The secondary winding is
the incoming line voltage to the desired level, but
shunted by a fixed ac capacitor. Upon application
also is the regulating means. The rectifiers, by use
of primary voltage, the secondary voltage increases
of conventional circuitry, convert the ac to dc. The
to the point at which that portion of the magnetic
filter circuit reduces the magnitude of the ripple to
core directly under the secondary winding ap
the desired specification level.
proaches saturation due to the capacitative load
The output ripple at full load and nominal input
connected across the secondary winding.
voltage is less than 1% RMS. The nominal output
voltage tolerance is 1% at nominal input voltage
F-1